BM5335 BM5335-A BM5335-F
Input rated power
1)
33.6 kW
Input rated current (I
eff
)
1)
53 A
DC link voltage (U
DC
)
1)
60 V - 760 V
DC link capacitance (internal) 1175 µF
DC link discharge time (internal DC link capacitance)
900 s
Output voltage
(U
AC
)
1) 3)
0 - 500 V
Output frequency at 4 kHz
4)
0 - 450 Hz
Output rated current
(I
AC
RMS)
1) 2) 5)11)
at 4 kHz
4)
60 A
Output rated current (I
AC
RMS)
1) 2) 5)11)
at 8 kHz
4)
42 A
Output rated current (I
AC
RMS)
1) 2) 5)11)
at 16 kHz
4)
24 A
Output peak current
(I
AC
RMS)
1) 5) 6)11)
at 4 kHz
4)
120 A
Output peak current
(I
AC
RMS)
1) 5) 6)11)
at 8 kHz
4)
84 A
Output peak current
(I
AC
RMS)
1) 5) 6)11)
at 16 kHz
4)
48 A
Short-time operation KB 200 %
Max. length of time peak current
6) 10)
Refer to ZLoad cycle accor
ding EN61800-6as from page
75
Power loss with regard to power supply Max. 460 W
Power loss with regard to
control voltage supply
(air-cooled)
7)
Max. 53 W -
Power loss with regard to
control voltage supply
(cold plate cooling)
7)
Max. 37 W - Max. 37 W
Current of the integrated brake control
(option)
8)
Max. 4.0 A
Cooling air requirement power heat sink 100 m
3
/h - -
Cooling air velocity power heat sink - > 5 m/s -
Cooling air requirement internal space of device 10 m
3
/h - -
Requirements of the water cooling - -
Refer to ZCool-
ingon page
56
Electrical data
Instruction handbook b maXX 5000
Document No.: 5.09021.16 Baumüller Nürnberg GmbH
70
of 328
3.4
Footnotes refer to Zpage 73.