Mounting and wiring
KL2xxx and KS2xxx32 Version: 3.0.0
Terminal housing High Density Housing
Wire size width (conductors with a wire end sleeve) 0.14 ... 0.75mm
2
Wire size width (single core wires) 0.08 ... 1.5mm
2
Wire size width (fine-wire conductors) 0.25 ... 1.5mm
2
Wire size width (ultrasonically “bonded" conductors)
only 1.5mm
2
(see notice [}31]!)
Wire stripping length 8 ... 9mm
Shielding
Shielding
Analog sensors and actors should always be connected with shielded, twisted paired wires.