3.7 Efficiency and losses
AC 100V AC 120V AC 230V
Efficiency typ. 93.2% 94.0% 95.2% At 24V, 10A, full load
Average efficiency
*)
typ. 92.7% 93.1% 93.9% 25% at 2.5A, 25% at 5A,
25% at 7.5A. 25% at 10A
Losses typ. 4.0W 4.0W 3.4W At 24V, 0A (no load)
typ. 9.0W 8.5W 7.5W At 24V, 5A (half load)
typ. 17.5W 15.3W 12.1W At 24V, 10A (full load)
*)
The average efficiency is based on assumptions for a typical application with the power supply unit
operating at 25% of the nominal load during 25% of the time, 50% of the nominal load during 25% of the
time, 75% of the nominal load during 25% of the time and 100% of the nominal load during the remaining
time.
Fig.7: Efficiency over output current; losses over output current
Fig.8: Efficiency over input voltage; losses over input voltage