3.13 Environment
Environment
Operating temperature
1)
-25°C to +70°C Reduction of the output power according to
Fig. Output current over ambient temperature
Storage temperature -40°C to +85°C For storage and transport
Output load reduction 6W/°C Between +55°C and +70°C
Humidity
2)
5 to 95% r.h. According to IEC 60068-2-30
Oscillation, sinusoidal
3)
2–17.8Hz: ±1.6mm;
17.8-500Hz: 2g 2 hours/axis
According to IEC 60068-2-6
Impacts
3)
30g 6ms, 20g 11ms 3 impacts/
direction, 18 impacts in total
According to IEC 60068-2-27
Installation altitude 0 to 2000m Without restrictions
2000 to 6000m Reduce output power or ambient
temperature, see Fig. Output current over
installation altitude
IEC 62477-1, overvoltage category II
Load reduction due to
installation altitude
15W/1000m or 5°C/1000m Above 2000m, see Fig. Output current over
installation altitude
Overvoltage category III According to IEC 62477-1, for altitudes up to
5000m
II Altitudes from 2000m to 6000m
Degree of pollution 2 According to IEC 62477-1, non-conductive
LABS-free The device does not release any silicones or other paint-wetting impairment
substances and is suitable for use in paint shops.
1)
The working temperature is identical to the room temperature or the ambient temperature and is defined as
the air temperature 2cm below the device.
2)
Do not energize when condensation is present
3)
Tested in conjunction with DIN rails according to EN 60715 with a height of 15mm and a thickness of
1.3mm and standard mounting position.
Fig.11: Output current over ambient temperature; output current over installation altitude