3.9 Terminals and wiring
The terminals are designed to be finger-safe according to IP20 and are suitable for field or factory wiring.
Technical data Input Output DC-OK signal
Connection cross-section e*: max. 6mm²
f*: max. 4mm²
a*: max. 4mm² (d<2.8mm)
e*: max. 6mm²
f*: max. 4mm²
a*: max 4mm² (d<2.8mm)
e*: max. 1.5mm²
f*: max. 1.5mm²
a*: max. 1.5mm²
(d<1.6mm)
Connection cross section
(AWG)
e*: AWG 20-10
f*: AWG 20-10
a* AWG 20-10 (d<2.8mm)
e*: AWG 20-10
f*: AWG 20-10
a* AWG 20-10
(d<2.8mm)
e*: AWG 28-16
f*: AWG 28-16
a*: AWG 28-16
(d<1.6mm)
Strip length 7mm / 0.28inch 7mm / 0.28inch 7mm / 0.28inch
e* = solid wire
f* = stranded wire
a* = with ferrule
Instructions
Use suitable copper cables that are designed for a minimum operating temperature of:
- 75°C for ambient temperatures up to 55°C and
- 90°C for ambient temperatures up to at least 70°C.
Observe national installation rules and regulations!
Make sure all individual wires of a strand enter the terminal connection!
Do not use the device without PE connection.
Unused terminal spaces should be tightened securely.
Ferrules are permissible.