EasyManua.ls Logo

Beckhoff PS1011-2410-0000 - Emc

Beckhoff PS1011-2410-0000
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data, mounting, wiring
PS1011-2410-0000 21Version: 1.0
3.12 EMC
The power supply is suitable for application in industrial environments as well as in residential, commercial
and light industrial areas and small businesses.
EMC interference immunity
Strong transients VDE 0160 Over the entire load range 750V, 0.3ms
EMC interference emission According to generic standards: EN 61000-6-4
Conducted interference emission, in-
put lines
EN 55011, EN 55015, EN 55022, FCC Part 15,
CISPR 11, CISPR 22
Class B
Conducted interference emission,
output lines
1)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Limit values for the DC power connection
according to EN 61000-6-3 not met
Interference emission EN55011, EN55022 Class B
Harmonic input current EN 61000-3-2 Met, class A limits
Voltage fluctuations, flicker EN 61000-3-3 Met, tested with non-pulsating constant
current loads.
This device complies with FCC Part 15.
Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must be
able to deal with any interference received, including interference that may cause undesired operation.
1)
for information only, not mandatory for EN 61000-6-3
Switching frequencies
PFC converter 60kHz to 140kHz Input load and output voltage dependent
Main converter 65kHz to 150kHz Output voltage and output load dependent