Technical data, mounting, wiring
PS1011-2410-000010 Version: 1.0
3 Technical data, mounting, wiring
3.1 AC input
AC input
AC input Nom. AC 100-240V Suitable for TN, TT and IT networks with alternating voltage
AC input range Min. 90-264Vac Continuous operation
Min. 264-300Vac For up to 500ms max.
Permissible voltage L or N to
earth
Max. 300Vac Continuous according to IEC 62477-1
Input frequency Nom. 50-60Hz ±6%
Turn-on voltage typ. 81Vac Static, see Fig. Input voltage range
Shut-down voltage typ. 63Vac/71Vac At zero load / nominal load, static value, see Fig. Input voltage range
External input protection
See recommendations in chapter External input protection [}28]
AC input AC100V AC120V AC230V
Input current typ. 2.60A 2.17A 1.18A At 24V, 10A, see Fig. Input current over output current
Power factor
1)
typ. 0.99 0.98 0.93 At 24V, 10A, see Fig. Power factor over output current
Crest factor
2)
typ. 1.6 1.7 2.0 At 24V, 10A
Start-up delay typ. 360ms 260ms 200ms See Fig. Switch-on behavior definitions
Rise time typ. 60ms 60ms 60ms At 24V, 10A constant current load, 0mF load capacity, see Fig. Switch-on
behavior definitions
typ. 230ms 230ms 230ms At 24V, 10A constant current load, 10mF load capacity, see Fig. Switch-on
behavior definitions
Turn-on overshoot Max. 200mV 200mV 200mV See Fig. Switch-on behavior definitions
1)
The power factor is the ratio of real (or active) power to apparent power in an AC circuit.
2)
The crest factor is the mathematical ratio of the peak value over the RMS value of the input current waveform.
Fig.1: Input voltage range; switch-on behavior definitions
Fig.2: Input current over output current; power factor over output current