Foreword
PS1011-2410-0000 9Version: 1.0
Safety instructions and installation requirements for the PS1011-2410-0000 power supply
DANGER
Danger of electric shock, fire, injuries, injuries resulting in death!
• Do not use the power supply without proper grounding (protective conductor). Use the terminal at the in-
put terminal strip for the earth connection, not one of the screws on the housing.
• Switch off the power supply before working on the device. Provide protection against unintentional re-
connection.
• Ensure proper wiring by following all local and national regulations.
• Do not modify or attempt to repair the device.
• Do not open the device, as high voltages are present inside.
• Avoid foreign bodies entering the housing.
• Do not use the device in damp locations or in areas where moisture or condensation is likely to occur.
• Do not touch the device when it is switched on or immediately after it has been switched off. Hot sur-
faces can cause burns.
Further notes on installation requirements
• This device contains no parts that require maintenance. If an internal fuse trips, this is due to an
internal defect.
• If any damage or malfunction occurs during installation or operation, turn off the power supply
immediately and return the device to the factory for inspection.
• Install the device on a DIN rail according to EN 60715, with the input terminals at the bottom of
the device.
• This device is designed for convection cooling and does not require an external fan. Do not ob-
struct the air circulation. No more than 15% of the ventilation grille may be covered (e.g. by cable
ducts)!
• Maintain the following installation distances: 40 mm at the top, 20 mm at the bottom and 5 mm
on the left and right are recommended if the device continuously runs at more than 50% of the
rated output. Increase this distance to 15 mm if the adjacent device is a heat source (e.g. an-
other power supply).