4
V4. 12. 2010
.
Subject to modification
Damper Actuator product overview
General Damper Actuator
General Damper Actuator
Open/Close, 3-point
AC/DC 24V 50/60Hz
Auxiliary switch built-in 1 SPDT
AC 100...240V 50/60Hz
AC 230V 50Hz (Open/Close)
Auxiliary switch built-in 1 SPDT
Modulating
AC/DC 24V 50/60Hz
Control signal DC 2(0)...10V, feedback DC 2...10V
AC 100...240V 50/60Hz
Running time
Shaft diameter
Sound power level
Electrical connection
Direction of rotation
Angle of rotation
Position indication
Degree of protection
EMC
Ambient temperature
Non-operation temperature
Cable 1m (-T: Terminal)
Manual override
Gear disengaging by pushbuttonGear disengaging by magnet
Selected by switch
Max. 95°, can be limited at both ends with mechanical adjustable end stops
Mechanical, plug-on
IP54 in any direction (-T: IP20)
CE according to 89/336/EEC
-30...+50°C
-40...+80°C
Humidity test
95% RH, non-condensing (to EN 60730-1)
* Only Open/Close, no 3-point.
** CMU24-SR-R: Control signal 2(0)V at the right side, and the left side is available on request.
CMU..
2Nm
CMU24(-F8/-F10)(-T)
CMU230(-F8/-F10)
CMU230(-F8/-F10)-RES*
CMU24-SR-R**
75s 150s
6...12.7mm
Max. 35dB(A)
LMU..
5Nm
LMU24(-F/-T)
LMU24-S
LMU230
LMU230-S
LMU24-SR
LMU230SR
6...20mm
Max. 35dB(A)
NMU..
10Nm
NMU24(-F/-T)
NMU24-S
NMU230
NMU230-S
NMU24-SR
NMU230SR
8...26mm
Max. 35dB(A)
SMU..
20Nm
SMU24(-F/-T)
SMU24-S
SMU230
SMU230-S
SMU24-SR
SMU230SR
10...20mm
Max. 48dB(A)
GMU..
40Nm
GMU24*
GMU230*
GMU24-SR
14...26mm
Max. 48dB(A)
LMQU..
8…26.7mm
NMQU.. SMQU..
Open/Close
AC 24V 50/60Hz, DC 24V
Modulating
AC 24V 50/60Hz, DC 24V
Control signal DC 2(0)…10V, feedback signal DC 2…10V
Running time
Shaft diameter
Sound power level
Manual override
Electrical connection
Direction of rotation
Angle of rotation
Position indication
Degree of protection
EMC
Ambient temperature
Non-operation temperature
Humidity test
4Nm
LMQU24
LMQU24-SR
2.5s
8Nm
NMQU24
NMQU24-SR
4.0s
16Nm
SMQU24
SMQU24-SR
7.0s
12…25.5mm
Max. 52dB(A)
Disengaging the gearing latch by means of a pushbutton, self-resetting
Cable 1m
Selected by switch
Max. 95°, can be limited at both ends with mechanical adjustable end stops
Mechanical, plug-on
IP54 in any direction
CE according to 2004/108/EC
-30…+40°C (without restrictions); +40…+50°C (with restrictions)
-40…+80°C
95% RH, non-condensing (to EN 60730-1)