EasyManua.ls Logo

Belimo CMU Series - SFU Series Mechanical Fail-Safe Actuators; SFU Series Technical Data and Dimensions

Belimo CMU Series
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V4. 12. 2010
.
Subject to modification
43
Technical data
Dimensions [mm]
Electrical data
Nominal voltage AC 24...240V 50/60Hz, DC 24...125V
Power consumption
Nominal voltage range
AC 19.2...264V, DC 20.4...126.5V
Functional data
Torque - Motor
Min. 20Nm @ nominal voltage
Min. 20Nm
Direction of rotation
Selectable by mounting L/R
Manual override
By manual override key
Angle of rotation
Max. 95
°
, limited on both sides
by means of adjustable, mechanical end stops
Running time - Motor
Sound power level - Motor
Max. 75s (0...20Nm)
Max. 20s @ -20...50
°
C/max. 60s @ -30
°
C
Max. 45dB(A)
Position indication Mechanical
Working conditions
Degree of protection
IP54
Ambient temperature
-30...+50
°
C
Non-operation temperature
-40...+80
°
C
Maintenance Maintenance-free
Dimensions / weight
Weight Approximately 2200g
Dimensions (LxWxH)
236x98x58mm
Humidity test
95% RH, non-condensing
Connection
Cable 1m, 2x0.75mm
2
Protection class
II (Totally insulated)
EMC
CE according to 2004/108/EC
Low voltage directive
Control pollution degree
Rated Impulse Voltage
Mode of operation
3
4kv
Type 1.AA
CE according to 2006/95/EC
7.0W @ running / 3.5W @ holding
Wire/transformer sizing
7.0VA @ AC 24V
8.5VA @ AC 120V
18.0VA @ AC 240V
- Spring return
- Spring return
Max. 62dB(A)
- Spring return
Mechanical Fail-Safe Damper Actuator SFU
Damper actuator for operating air control dampers in ventilation
and air-conditioning systems for building services installations
ΓTorque: 20Nm
ΓNominal voltage: AC 24...240V
DC 24...125V
ΓControl: Open/Close
59
20
85
2-F
RON
T
32 
162
172
182
236
98
80
Standard :
¾”- clamp (with insert)
Length
≥85
≥15
≥15
≥15
10...22 10
10
10...22 14...25.4
14...25.4
Optional 1:
1”- clamp (without insert)
Length
≥85
½”
Damper shaft Length
≥85
10...19
14...20
12...1819...25.4
19...25.4 12...18
14...20
10...19
Damper shaft
Damper shaft
Optional 2:
- clamp (optional via configuration)

Related product manuals