10. Technical data
10.1 Tabular presentation
( )* = Factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Definitions:
Supply circuit (IC2) ....................................................................................................................................... A1, A2
Output circuit (IC3)................................................................................................................................... 11, 14, 24
Control circuit (IC4) ............................................................................................ Up, KE, T/R, A, B, AK1, GND, AK2
Rated voltage.......................................................................................................................................................... 240 V
Overvoltage category.....................................................................................................................................................III
Rated impulse voltage:
IC2/(IC3-4) ......................................................................................................................................................... 4 kV
IC3/(IC4) ............................................................................................................................................................. 4 kV
Rated insulated voltage:
IC2/(IC3-4) ...................................................................................................................................................... 250 V
IC3/(IC4) .......................................................................................................................................................... 250 V
Polution degree.............................................................................................................................................................. 3
Protective separation (reinforced insulation) between:
IC2/(IC3-4) .............................................................................................................. Overvoltage category III, 300 V
IC3/(IC4) .................................................................................................................. Overvoltage category III, 300 V
Voltage test (routine test) according to IEC 61010-1:
IC2/(IC3-4) ................................................................................................................................................ AC 2.2 kV
IC3/(IC4) .................................................................................................................................................... AC 2.2 kV
Supply voltage
Supply voltage U
s
...................................................................................................... AC 100…240 V/DC 24…240 V
Tolerance of U
s
........................................................................................................................................ -30…+15 %
Frequency range U
s
...................................................................................................................................... 47…63 Hz
Power consumption ............................................................................................................................... ≤ 3 W, ≤ 9 VA