www.blaubergventilatoren.de
S21
16
Air ow
Go to Menu ( ) - Engineering menu - Air ow.
This menu section enables setting the air flow values for the Standby mode, speed 1,2,3 pre-sets
as well as the Boost and Fireplace modes.
If the air flow value selected for the Standby mode is larger than 0 %, the temperature control
function for this mode according to setpoint selected (only +15°С temperature is maintained
provided the unit is equipped with a heater and the Heating or Auto mode is selected in the Basic
settings -> Temperature) as well as the air quality management function will not be available.
If the unit is controlled with an external 0-10 V input or if the PI controller is triggered by a humidity,
CO
2
, РМ2.5 or VOC level alarm, the balance between the supply and extract air will correspond to
speed 1,2,3 pre-sets.