EasyManua.ls Logo

bolid S2000-2 - Connecting Alarm Loops

bolid S2000-2
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Orion ISS
www.bolid.com 66
CONNECTING ALARM LOOPS
In all S2000-2 operation modes except the Swing-beam Barrier (see above) LOOP1 and LOOP2 ter-
minals of the S2000-2 controller are used to connect intruder alarm loops (see Alarm Loops Section
of this Manual).
Figure 17 shows how to bring detectors with normally closed and normally open contacts into a
S2000-2 alarm loop.
8.2 kOhm
LOOP
S2000-2
LOOP+
Figure 17. NO and NC Intruder Detectors to the S2000-2 Connection Diagram
Resistance of the loop wires must not exceed 1 kOhm, excluding the terminating resistor.
Leakage resistance between the loop wires or between each wire and ground must not be less than
20 kOhm.
The S2000-2 controller provides arming a loop if the resistance of this loop including terminating re-
sistance 8.2 kOhm ranges from 5 kOhm ± 10% to 11 kOhm ± 10%.

Table of Contents