INGENIO COMPACT 10-20kVA Руководство по быстрому монтажу
Installation and start-up of INGENIO COMPACT 10÷20 kVA
OMS90052 РЕД. / REV.A
33
Recommended Size of Cables
Capacity
Mains Input
(1)
Output/ Bypass Input
(1)
External Battery
(1)
R/S/T/N PE R/S/T/N
(2)
PE +/-/N PE
10kVA 5 mm
2
3 mm
2
5 mm
2
3 mm
2
8 mm
2
3 mm
2
20kVA 8 mm
2
5 mm
2
6 mm
2
5 mm
2
16
mm
2
8 mm
2
(1)
The recommended maximum length of cabling is less than 10meters.
(2)
Please over size neutral line N by 1.7 times of the phase line for non-linear loads.
Recommended Circuit Breaker Size
Input/
Output
Voltage
Output
Power
Mains Input
(1)
Output/Bypass
Input
(1)
380 V
10kVA/10KW
30 A 25 A
20kVA/20KW
65 A 50 A
400 V
10kVA/10KW
30 A 25 A
20kVA/20KW
60 A 50 A
415 V
10kVA/10KW
30 A 25 A
20kVA/20KW
55 A 50 A
(1)
The sizing takes into account 150% overload capacity.