1.3.2 Cold Start
(5) This is optional function and only available when the UPS install DC Cold Start
Kit.
(6) User can start-up UPS by battery when main input power is not available.
(7) Select CommandOperationCold start precharge ready on LCD
display.
(8) Select Normal mode to start UPS.
1.3.3 Shutdown
(2) Select CommandOperationShutdown on LCD display.
1.3.4 Switch to bypass
(3) Select CommandOperationShutdown converter except bypass
on LCD display.
(4) The Inverter will be shutdown and bypass will supply the power to the load. If
the battery is disconnected, Rectifier and Charger will be shutdown as well.
1.3.5 Switch from normal mode to maintenance bypass
(7) Select CommandOperationShutdown converter except bypass on
LCD display.
(8) The Inverter will be shut down and bypass will supply the power to the load
(9) Open the Main Input and Battery Switches
(10) Close the maintenance bypass switch
(11) Open Output and Bypass switch
(12) Wait at least for 10min