INGENIO COMPACT 10-20kVA Руководство по быстрому монтажу
INGENIO COMPACT 10-20kVA Quick installation guide
38 OMS90052 РЕД. / REV. A
1.3 OPERATION PROCESSES
1.3.1 Normal Mode Start-up
Warning!
Please don’t close the battery line switch/fuses before start-up
the rectifier of UPS if the UPS don’t install optional DC Cold
Start Kit.
(7) Close UPS Mains Input and Bypass Input Switches.
(8) Select →Command→Operation→Normal mode on LCD display.
(9) Return to Mimic Display. Wait for few minutes, the rectifier will be started.