EasyManua.ls Logo

Bosch 520 Series - Page 22

Bosch 520 Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22 en | Programming Automatic Detectors LSN improved
2019.11 | 4.0 | F.01U.025.877 Operation Guide Bosch Sicherheitssysteme GmbH
Operating location and recommended setting for optical fire
detector (FAP‑O520) selectable via the programming software
Sensitivity Ounit
Production facilities low
Office (daily operation) medium
School / kindergarten medium
Theaters / concert halls medium
Office (no traffic) high
Computer room high
High-board warehouse without vehicle traffic with internal
combustion engines
high
Notice!
For execution of the function test for the FAP‑O520 and FAP‑OC520 detector, the detector
must be switched to test mode. This can be carried out via the fire panel or via the reed
switch at the detector with the help of a magnet (see Maintenance and Service, page 23).

Related product manuals