32.4 Cross points
Points can be assigned to cross point groups. When a point in a
cross point group detects an alarm, the control panel starts the
cross point timer. If a second point in the same cross point group
detects an alarm while the cross point timer is active, the control
panel sends alarm reports for both points.
If a single cross point detects an alarm and stays in alarm
throughout the cross point timer, the control panel sends an
alarm report only for that point. If a single point in a cross point
group detects an alarm and restores while the timer is still active,
the system sends an unverified event for that point. A second
alarm on the first point does not create an alarm event, but
rather an unverified event.
Cross points are:
enabled on my system.
disabled on my system.
212 en | Options Control Panels
2015.01 | 02 | F.01U.307.371 Bosch Security Systems, Inc.