36
|
Installation Instructions
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump - BTC 761703103 A (11.2022)
13.12 Temperature and Resistance Relationship Tables (for Sensors)
TEMP F TEMP C RESISTANCE kΩ VOLTS DC TEMP F TEMP C RESISTANCE kΩ VOLTS DC
-5 -20.6 107.732 4.65 90 32.2 7.225 2.36
0 -17.8 93.535 4.60 95 35.0 6.401 2.21
5 -15.0 79.521 4.54 100 37.8 5.683 2.07
10 -12.2 67.795 4.47 105 40.6 5.057 1.93
15 -9.4 57.948 4.39 110 43.3 4.509 1.79
20 -6.7 49.652 4.30 115 46.1 4.028 1.67
25 -3.9 42.645 4.21 120 48.9 3.606 1.55
30 -1.1 36.710 4.10 125 51.7 3.233 1.43
40 4.4 27.386 3.86 130 54.4 2.902 1.32
45 7.2 23.732 3.73 135 57.2 2.610 1.22
50 10.0 20.610 3.59 140 60.0 2.350 1.13
55 12.8 17.939 3.45 145 62.8 2.119 1.04
60 15.6 15.648 3.30 150 65.6 1.914 0.96
65 18.3 13.681 3.15 155 68.3 1.731 0.88
70 21.1 11.987 2.99 160 71.1 1.574 0.82
75 23.9 10.527 2.83 165 73.9 1.416 0.75
80 26.7 9.265 2.67 170 76.7 1.276 0.68
85 29.4 8.172 2.52
Table 34 for T3, T4, Th, T3L, T1, T2