CP/BP Series
Installation and Maintenance Manual
Revised 01-11
6 720 220 045

Questions and Answers

  • S
    Sharon MeyersAug 10, 2025
    Why my Bosch BP070 is not running?
    • L
      Lori RogersAug 10, 2025
      Your Bosch Heat Pump might not be running due to several reasons. First, ensure that the power supply is on and the disconnect is closed. Check the fuse and replace it or reset the circuit breaker if blown, ensuring you use the correct fuses. If the voltage supply is lower than specified on the unit's data plate, contact your local power company. Also, the thermostat could be miswired or faulty. Try setting the fan to 'ON' to see if it runs. Test the cooling and heating modes by adjusting the thermostat to the lowest and highest temperature settings, respectively. If the blower or compressor doesn't run in any of these cases, check the thermostat wiring and voltage at the low voltage terminal strip. Replace the thermostat if it's defective.
  • E
    Erin FaulknerAug 19, 2025
    What to do if my Bosch Heat Pump turns off due to high pressure?
    • K
      Kari GuzmanAug 20, 2025
      If your Bosch Heat Pump shuts off due to high pressure, it could be caused by several factors. In cooling mode, check for a lack of or inadequate water flow, ensure the entering water temperature isn't too warm, and inspect for a scaled or plugged condenser. In heating mode, verify adequate airflow by checking if the blower is working, the filter is clogged, or there are restrictions in the ductwork. The unit might also be overcharged with refrigerant, requiring you to reclaim refrigerant, evacuate, and recharge it with the factory-recommended amount. Finally, check for a defective or improperly calibrated high-pressure switch.
  • Y
    ystephensAug 26, 2025
    Why does my Bosch BP070 shut off on low pressure control?
    • S
      Steven SavageAug 26, 2025
      If your Bosch Heat Pump shuts off due to low pressure, the suction pressure might be too low. In cooling mode, check for a lack of or inadequate airflow, ensure the entering air temperature isn't too cold, and inspect for a blower malfunction, clogged filter, or ductwork restrictions. In heating mode, verify adequate water flow and ensure the entering water temperature isn't too cold, also check for a scaled or plugged condenser. The unit may also be low on refrigerant, requiring a check for leaks, repair, evacuation, and recharge with the factory-recommended charge. Lastly, examine the low-pressure switch for defects or improper calibration.
  • S
    Sara OsborneAug 30, 2025
    What to do if the blower works but the compressor doesn't in my Bosch Heat Pump?
    • M
      Mr. Darrell PeckAug 30, 2025
      If the blower in your Bosch Heat Pump is running, but the compressor is not, start by checking the thermostat settings, calibration, and wiring. Inspect the wiring at the compressor, capacitor, and contactor for any loose or broken wires. Check the UPM board red default L.E.D. for Blink Codes. If the compressor is cool and the overload won't reset, it likely needs to be replaced. A compressor motor grounded or open windings can also cause this issue, requiring compressor replacement. After the compressor cools, check the continuity of the compressor windings; if they are open, replace the compressor.
  • A
    Ashley IrwinSep 4, 2025
    How to fix a Bosch BP070 that short cycles?
    • E
      Elizabeth HurleySep 4, 2025
      If your Bosch Heat Pump is short cycling, it might be due to several reasons. The unit could be oversized, requiring a recalculation of heating or cooling loads. The thermostat may be installed near a supply air grill, necessitating its relocation, or the heat anticipator may need readjustment. Also, check the low-pressure switch for defects or improper calibration.
  • D
    dhintonNov 14, 2025
    How to troubleshoot insufficient cooling or heating in my Bosch Heat Pump?
    • W
      wjohnsonNov 14, 2025
      Insufficient cooling or heating in your Bosch Heat Pump can stem from several causes. First, the unit might be undersized, requiring a recalculation of heating and cooling loads, and possibly adding insulation. Check for air leaks in ductwork, doors, or windows. Ensure adequate airflow and replace any dirty filters. A low refrigerant charge can also cause inefficiency. Inspect the compressor for defects—if the discharge is too low and suction pressure too high, the compressor may need replacement. Other potential issues include a defective reversing valve, incorrect operating pressures (compare to the unit's pressure/temperature chart), a restricted or defective TXV, or contamination of the refrigerant system with moisture or non-condensables, which would require reclaiming the refrigerant...