18 CP/BP Series Unit Specications
Table 5: Air Temperature Rise/Fall
Entering Fluid
Temp °F
COOLING HEATING
Entering Air Temp °F Air Temp Drop °F Entering Air Temp °F Air Temp Rise °F
30
60 16-8 - 25.1
70 15.9 - 23.7
80 14.8 - 22.1
40
75/63 21.9 - 27.2 60 20.0 - 28.5
80/67 22.9 - 28.5 70 19.0 - 27.0
85/71 23.8 - 29.5 80 17.7 - 25.2
50
75/63 20.5 - 25.8 60 23.3 - 32.8
80/67 21.5 - 27 70 22.0 - 31.0
85/71 22.3 - 28.1 80 20.5 - 29.0
60
75/63 19.2 - 24.7 60 26.5 - 37.1
80/67 20.1 - 25.8 70 25.1 - 35.1
85/71 20.9 - 26.8 80 23.4 - 32.7
70
75/63 17.9 - 23.8 60 29.8 - 41.4
80/67 18.7 - 24.9 70 28.2 - 39.1
85/71 19.5 - 25.8 80 26.3 - 36.4
80
75/63 16.6 - 23.0 60 32.7 - 45.7
80/67 17.4 - 24.0 70 30.9 - 43.1
85/71 18.1 - 25.0 80 28.8 - 40.2
85
75/63 16.0 - 22.6
80/67 16.8 - 23.6
85/71 17.4 - 24.5
90
75/63 15.4 - 22.2
80/67 16.1 - 23.2
85/71 16.8 - 24.1
100
75/63 14.2 - 21.4
80/67 14.9 - 22.4
85/71 15.4 - 23.3
110
75/63 13.0 - 21.1
80/67 13.7 - 22.1
85/71 14.2 - 23.0