RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (2016/10)
OUTDOOR UNIT INSTALLATION | 7
Curve diagram of static pressure, air flow volume.
Table.4-5 Unit: mm Table.4-6 Unit: mm
A A≥300 A A≥300
B B≥250 B B≥250
C C≤3000 C C≤3000
D 750≤D≤760
θ
θ≤15°
θ
θ≤15°
NOTE
Before installing the air deflector, please ensure the fan grill has
been taken off.
Once air deflector has been installed, the air volume, cooling/
heating capacity will decrease. The maximum angle allowed for the
shutter is 15 degrees.
Only one bend set is allowed.
Install anti vibration pads in between the unit and air deflector.
Fig. 4-22
12 ST3.9 self-threading screws
Remove the fan grills
10
01
12-Ø3.2
393
567
1250
411 411213
411 411213
Fig. 4-23
9500
10000
10500
11000
11500
12000
12500
0 5 10 15 20 25
Fig. 4-24
8/10HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
10500
11000
11500
12000
12500
13000
13500
0 5 10 15 20 25
Fig. 4-25
12HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
12500
13000
13500
14000
14500
15000
15500
0 5 10 15 20 25
Fig. 4-26
14/16HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
B
0921
C
1210
A
Fig. 4-27
Example B
Support
Radius
Air outlet louver dimension (optional)
725
Ø3.2
393
567
1250
411 411
213
411 411213
Fig. 4-28
Fig. 4-29
12 ST3.9 self-threading screws
Remove the fan grills