Climate 5000 8736862495(2015/07)
Unit maintenance | 17
No.
Inspection and maintenance
items
Maintenance measures
1
M
3
M
6
M
1
Y
2
Y
Remarks
Inspection and
maintenance
intervals
1 Unit and base connection
1.1
Check tightness of bolt
connections between unit and
base
Tighten if necessary
1.2
Check the wearing condition
of the absorbtion gasket
between unit and base
Replace if necessary
2 Unit box body
2.1
Check the scale, damage and
corrosion of the unit box body
Clean and rectify
3 Filter
3.1
Check the scale, damage and
corrosion
Clean and rectify
According
to the
operating
condition
3.2
Check the pressure difference
at both sides
When the clean filter
resistance exceeds the
maximum allowable value,
replace the filter
4 Coil
4.1
Check the scale, damage and
corrosion
Clean and rectify
4.2 Check the ability state
4.3
Check the connection leakage
between inlet and outlet pipe
Seal if necessary
5 Water baffle, drain pan
5.1 check water baffle
5.2
Check the draining state of
the drain pan
Clean
6 Heat exchanger
6.1 Plate heat recovery
6.1.1
Check the scale, damage and
corrosion
Clean and rectify
6.1.2
Check the fresh air and return
air for serialization
Rectify
6.2 Wheel heat recovery
6.2.1
Check the balance of the
wheel
Adjust if necessary
6.2.2
Check the drive working
condition
Tab. 6-1 Inspection and maintenance items 1