6.4 Air flow insufficient
6.5 Cooling capacity too small
6.6 Leakage
Climate 5000 8736862495(2015/07)
Fault analysis and troubleshooting | 21
Tab. 7 Fault analysis and troubleshooting table
Adjust cold water temperature
Cold water
temperature too high
Cold water flow too low
Cold water
Adjust cold water flow
Air flow insufficient
Vane run reversely Re-adjust motor wiring
In
g
ress of im
p
urities Check and clean
Air duct high resistance Reduce resistance
The opening of air
valve too small
Check and adjust
Fan speed low Increase fan speed
Dust Clean
Filter blocked Clean, replace
Coil fin blocked Clean
Leaking outside
the unit
Pipe connection loose Tighten
Condensate water
outlet blocked
Clean
Unreasonable design
of drain seal
Adjust hydraulic seal size
Water splashing
inside the unit
Humidifier abnormal
Repair in accordance with
the specific reason
Steam pressure
abnormal
Adjust
Low humidification Increase air supply speed
Low air flow Increase air flow appropriately
Air flow
Coil
Coil blocked Clean to make it unblocked
Cause Remed
y
Cause Remed
y
Cause Remed
y