On-site configuration
55
Climate 5000L • Climate 5000i U/L – 6721841492 (2022/03)
4 On-site configuration
4.1 DIP switch setting
WARNING
Risk to life from electric shock!
Touching live electrical parts can cause an electric shock.
▶ Before working on electrical parts, disconnect all phases of the
power supply (fuse/circuit breaker) and lock the isolator switch to
prevent unintentional reconnection.
All DIP switches have been configured before delivery. The default
setting is highlighted bold.
▶ Only professional maintenance personnel should change these
settings.
▶ Improper DIP switch settings may cause condensation, noise, or
unexpected system malfunction.
CL5000iU 4CC ...
CL5000iL 4C ...
Definition of DIP switch 0/1:
Definition 0
Definition 1
ENC1 Code Capacity setting
1)
1) Default depending on the model
020
1 26
2 32 - 35
4 36 - 53
5 54 - 71
7 72 - 90
8 91 - 105
9 109 - 140
A 141 - 160
B 161 - 200
S1 S1 Setting S2 Network address
0 - F 0 - 15
1)
1) Default
0 - F 16 - 31
0 - F 32 - 47
0 - F 48 - 63
DIP switch Definition of DIP Switches
1)
1) Default highlighted in bold
Fan OFF temperature when heating (anti-cold air function)
SW1 • [00]: 24°
• [01]: 8 °C
• [10]: 15 °C
• [11]: Reserved
Behaviour of the fan once the room target temperature has been
reached
SW2 • [0]: Fan off
• [1]: Fan on (anti-cold air function deactivated)
Auto restart
SW3 • [0]: Note setting
• [1]: Do no note setting
Set master and slave unit
SW5 • [00]: Master unit only, no slave unit
• [01]: Master unit (heating)
• [10]: Master unit (cooling)
• [11]: Slave unit
Temperature compensation (heating)
SW6 • [00]: 6 °C
• [01]: 2 °C
• [10]: 4 °C
• [11]: Reserved
DIP switch Definition of DIP Switches
1)
1) Default highlighted in bold
Fan OFF temperature when heating (anti-cold air function)
SW1 • [00]: 24 °C
• [01]: 15 °C
• [10]: 8 °C
• [11]: Reserved
Behaviour of the fan once the room target temperature has been
reached
SW2 • [0]: Fan off
• [1]: Fan on (anti-cold air function deactivated)
Auto restart
SW3 • [0]: Automatic restart on
• [1]: Automatic restart off
Set master and slave unit
SW5 • [00]: Master unit only, no slave unit
• [01]: Master unit (heating)
• [10]: Master unit (cooling)
• [11]: Slave unit
Temperature compensation (heating)
SW6 • [00]: 6 °C
• [01]: 2 °C
• [10]: 4 °C
• [11]: Reserved
Default cooling and heating or only cooling
SW7 • [0]: Cooling and heating
• [1]: Cooling only