Technical data
Climate 5000L • Climate 5000i U/L – 6721841492 (2022/03)
60
9Technical data
Table 14 Technical data
Set CL5000iL-Set 35 4CCE CL5000iL-Set 53 4CCE CL5000iL-Set 70 4CE
Indoor Unit CL5000iU 4CC 35 E CL5000iU 4CC 53 E CL5000iU 4C 70 E
Outdoor Unit CL5000L 35 E CL5000L 53 E CL5000L 70 E
General
Refrigerant – R32 R32 R32
Design pressure (max./min.) MPa 4.3/1.7 4.3/1.7 4.3/1.7
Cooling
Rated output kW 3.52 5.28 7.03
Rated output kBtu/h 12 18 24
Power input at rated output W 1010 1633 2320
Cooling load (Pdesignc) kW 3.5 5.3 7
Output (min. - max.) kW 0.85-4.11 2.90-5.59 3.30-7.91
Power input (min. - max.) W 168-1434 720-2088 780-2748
Max. current consumption A 4.45 7.2 10.2
Energy efficiency class A++ A++ A++
Coefficient of Performance in cooling mode (SEER) W/W 6.6 6.3 6.2
Heating
Rated output kW 3.81 5.57 7.62
Rated output kBtu/h 13 19 26
Power input at rated output W 1019 1540 1900
Heating load (Pdesignh) kW 2.7 4.2 6
Output (min. - max.) kW 0.47-4.31 2.37-6.10 2.81-8.94
Power input (min. - max.) W 124-1376 700-1930 610-2700
Max. current consumption A 4.73 6.8 8.5
Energy efficiency class A+ A+ A+
Coefficient of Performance in heating mode (SCOP) W/W 4.1 4.0 4.0
Indoor unit
Ex-protected ceramic fuse on main board T 20A/250V T 20A/250V T 20A/250V
Power infeed V/Hz 220-240 / 50
single phase
220-240 / 50
single phase
220-240 / 50
single phase
Volumetric flow rate (high/medium/low) m
3
/h 569/485/389 680/584/479 1247/1118/992
Sound pressure level (high/medium/low/noise reduction) dB(A) 42/37.5/34.5/28.5 45.4/44/39/31.6 50/47.5/42/38
Sound power level (high) dB(A) 57 59 59
Permissible ambient temperature (cooling/heating) °C 16...32/0...30 16...32/0...30 16...32/0...30
Total net weight kg 18.8 18.5 27.6
Net weight (casing/cover) kg 16.3/2.5 16.0/2.5 21.6/6.0
Outdoor unit
Maximum power consumption W 1850 2950 3700
Maximum power consumption A 9 13.5 19
Ex-protected ceramic fuse on main board T 20A/250V T 20A/250V T 20A/250V
Power infeed V/Hz 220-240 / 50
single phase
220-240 / 50
single phase
220-240 / 50
single phase
Vol. flow rate m
3
/h 2200 2100 3500
Sound pressure level dB(A) 53.6 56 60
Sound power level dB(A) 62 65 69
Permissible ambient temperature (cooling/heating) °C -15...50/-15...24 -15...50/-15...24 -15...50/-15...24
Net weight kg 26.6 32.5 43.9