Table 15 Technical data
Set CL5000iL-Set 88 4CE CL5000iL-Set 105 4CE CL5000iL-Set 105 4CE-3
Indoor Unit CL5000iL 4C 88 E CL5000iL 4C 105 E CL5000iL 4C 105 E
Outdoor Unit CL5000L 88 E CL5000L 105 E CL5000L 105 E-3
General
Refrigerant – R32 R32 R32
Design pressure (max./min.) MPa 4.3/1.7 4.3/1.7 4.3/1.7
Cooling
Rated output kW 8.8 10.5 10.5
Rated output kBtu/h 30 36 36
Power input at rated output W 2750 3950 4000
Cooling load (Pdesignc) kW 8.79 10.55 10.55
Output (min. - max.) kW 2.23-9.38 2.70-11.43 2.70-11.43
Power input (min. - max.) W 190~3000 900-4200 890-4150
Max. current consumption A 12.0 17.5 6.5
Energy efficiency class A++ A++ A++
Coefficient of Performance in cooling mode (SEER) W/W 6.6 6.7 6.3
Heating
Rated output kW 9.38 11.14 11.14
Rated output kBtu/h 32 38 38
Power input at rated output W 2450 3000 3000
Heating load (Pdesignh) kW 7.8 8.5 8.0
Output (min. - max.) kW 2.70-9.73 2.78-12.30 2.78-12.66
Power input (min. - max.) W 430-2550 800~3950 780~4000
Max. current consumption A 11.0 13.5 5.0
Energy efficiency class A+ A+ A
Coefficient of Performance in heating mode (SCOP) W/W 4.2 4.0 3.9
Indoor unit
Ex-protected ceramic fuse on main board T 30A/250V T 30A/250V T 30A/250V
Power infeed V / Hz 220-240 / 50
single phase
220-240 / 50
single phase
220-240 / 50
single phase
Volumetric flow rate (high/medium/low) m
3
/h 1700/1530/1300 1700/1530/1300 1700/1530/1300
Sound pressure level (high/medium/low/noise reduction) dB(A) 50.5/48/46/40 51/48/46/40.5 510/49/46/40
Sound power level (high) dB(A) 63 64 64
Permissible ambient temperature (cooling/heating) °C 16...32/0...30 16...32/0...30 16...32/0...30
Total net weight kg 30.6 33.2 33.2
Net weight (casing/cover) kg 24.6/6.0 27.2/6.0 27.2/6.0
Outdoor unit
Maximum power consumption W 4500 5000 5000
Maximum power consumption A 20 22.5 10
Ex-protected ceramic fuse on main board T 30A/250V T 30A/250V T 30A/250V
Power infeed V / Hz 220-240 / 50
single phase
220-240 / 50
single phase
380-415 / 50
three phase
Vol. flow rate m
3
/h 3800 4000 4000
Sound pressure level dB(A) 62 63 63
Sound power level dB(A) 70 70 70
Permissible ambient temperature (cooling/heating) °C -15...50/-15...24 -15...50/-15...24 -15...50/-15...24
Net weight kg 52.8 66.9 80.5