Technical data
Climate 5000L • Climate 5000i U/L – 6721841492 (2022/03)
62
Table 16 Technical data
Set CL5000iL-Set 125 4CE CL5000iL-Set 140 4CE-3 CL5000iL-Set 160 4CE-3
Indoor Unit CL5000iL 4C 125 E CL5000iL 4C 140 E CL5000iL 4C 160 E
Outdoor Unit CL5000L 125 E CL5000L 140 E-3 CL5000L 160 E-3
General
Refrigerant – R32 R32 R32
Design pressure (max./min.) MPa 4.3/1.7 4.3/1.7 4.3/1.7
Cooling
Rated output kW 12.1 14.0 15.3
Rated output kBtu/h 41 48 52
Power input at rated output W 4200 4650 5000
Cooling load (Pdesignc) kW 12.02 14.07 15.24
Output (min. - max.) kW 2.93-12.31 3.52-15.83 4.10-16.71
Power input (min. - max.) W 680-4350 800-5900 980-6200
Max. current consumption A 18.8 8.1 8.6
Energy efficiency class A++ A++ A++
Coefficient of Performance in cooling mode (SEER) W/W 6.1 6.1 6.3
Heating
Rated output kW 13.48 16.12 18.17
Rated output kBtu/h 46 55 62
Power input at rated output W 3700 4580 5550
Heating load (Pdesignh) kW 9.5 11.0 11.9
Output (min. - max.) kW 3.37-14.07 4.10-17.29 4.40-19.9
Power input (min. - max.) W 750~4250 900 – 5500 1020 – 6700
Max. current consumption A 16.3 8.0 9.6
Energy efficiency class A+ A+ A+
Coefficient of Performance in heating mode (SCOP) W/W 4.0 4.0 4.0
Indoor unit
Ex-protected ceramic fuse on main board T 30A/250V T 30A/250V T 30A/250V
Power infeed V / Hz 220-240 / 50
single phase
220-240 / 50
single phase
220-240 / 50
single phase
Volumetric flow rate (high/medium/low) m
3
/h 1900/1750/1600 1900/1750/1600 2000/1850/1650
Sound pressure level (high/medium/low/noise
reduction)
dB(A) 52.5/50/47.5/40 52.5/50.5/48/41.5 54.5/52/49.5/44
Sound power level (high) dB(A) 66 66 66
Permissible ambient temperature (cooling/heating) °C 16...32/0...30 16...32/0...30 16...32/0...30
Total net weight kg 35.3 35.3 35.3
Net weight (casing/cover) kg 29.3/6.0 29.3/6.0 29.3/6.0
Outdoor unit
Maximum power consumption W 5000 6900 7500
Maximum power consumption A 22.5 13 14
Ex-protected ceramic fuse on main board T 30A/250V T 30A/250V T 30A/250V
Power infeed V / Hz 220-240 / 50
single phase
380-415 / 50
three phase
380-415 / 50
three phase
Vol. flow rate m
3
/h 4000 7500 7500
Sound pressure level dB(A) 63 63.5 64
Sound power level dB(A) 72 74 75
Permissible ambient temperature (cooling/heating) °C -15...50/-15...24 -15...50/-15...24 -15...50/-15...24
Net weight kg 71 103.7 107