Fire System | User’s Guide | 11.0 System Functions
Bosch Security Systems, Inc. | 8/06 | F01U011793B 28
Faulting a point more than once does not increment the
test count. However, the keypad emits a brief tone and
displays the point text each time you fault the point,
allowing you to test multiple devices assigned to one
point.
5. When all points are tested, 0 PTS TO TEST appears.
Press [ESC]. The display shows ALL PTS TESTED
briefly before returning to idle text.
6. To see any remaining untested points during the Fire
Test:
a. Press the [ESC] key and VIEW UNTESTED ?
appears.
b. Press [ENT]. The display shows # PTS UNTESTED.
c. Press [NEXT] to see a list of the points that were not
yet tested.
d. Press the [NEXT] key to move through this list.
e. To resume the Fire Test, press [ESC]. ## PTS TO
TEST appears.
7. Press [ESC] twice to leave the Fire Test mode.
Automatic time-out returns the system to idle text: If
there is no point or keypad activity for 20 minutes, the fire
test ends automatically. The keypad returns to idle text.