EasyManua.ls Logo

Bosch D7212GV2 - Page 30

Bosch D7212GV2
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D7212GV2 | Operation and Installation Guide | 8.0 On-Board Points
30 Bosch Security Systems, Inc. | 5/05 | F01U003805B
Figure 10: Wiring for Installation Using the Ademco AB-12 Bell/Housing
1
2
3
4
5
6
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
1
2
3
4
5
6
7
8
9
10
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
PROGRAMMABLE
ALARM OUTPUTS
Term inals
Requires Optional
Model D136 Relay
In ALT ALARM
& SW AUX
&
78
GROUND FAULT DETECT
Enabled
Disabled
VOLTAGE RANGES
Open 3.7 - 5.0 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
1211 13
Point 1 Point 2
1514 16
Point 3 Point 4
1817 19
Point 5 Point 6
2120 22
Point 7 Point 8
D7212GV2
TELCO
RING
TIP
PHONE LINE
SEIZED
PHONE
LED
RED
ON when
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO CORD
MODEL D161
1
2
3
4
5
1 - Bell
2 - Inner bell box lining
3 - Outer bell box
4 - Bell tampers
5 - 220 k
0.5 W EOL resistor (provided with the
Ademco AB-12 Bell/Housing)

Table of Contents