D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
32 Bosch Security Systems, Inc. | 11/05 | F01U011024B
Table 17: Point Type and Point Response Selections
Point Type Selections
Point Response
Selections
1
0 1 2 3 4 5 6 7 8 9 A B C D E F
0 24-Hour 6 O/C Point
Open I I I I D D I I D I I I I I T
1 Perimeter 7 D279 (O/C Non-Priority)
Armed
2
Short I I I I I I D D D I I I I I I
2 Interior 8 D279 (O/C Priority) Open T T T I I T I T
3 Interior Follower 9 Easikey
Disarmed
2
Short T T T I T I I
4 Keyswitch Maintained Open I T I T I T S T S S
5 Keyswitch Momentary
24-Hour
3
Short I I T T I T T S S S
Not
Applicable
1
Selections: D = Delayed Response, I = Instant Alarm, S = Supervisory,
T = Trouble, Blank = No Response
2
For point types 1 through 3 only.
3
For point type 0 only.
Table 18: Point Assignments
POPIT Switch
Setting
Point
#
001
002
003
004
005
006
007
Points
1 through 8
are on-board
points.
008
0 1 2 3 4 5 6 009
0 1 2 3 4 5 _ 010
0 1 2 3 4 _ 6 011
1 2 3 4 _ _ 012
0 1 2 3 _ 5 6 013
0 1 2 3 _ 5 _ 014
0 1 2 3 _ _ 6 015
0 1 2 3 _ _ _ 016
0 1 2 _ 4 5 6 017
0 1 2 _ 4 5 _ 018
0 1 2 _ 4 _ 6 019
0 1 2 _ 4 _ _ 020
0 1 2 _ _ 5 6 021
0 1 2 _ _ 5 _ 022
0 1 2 _ _ _ 6 023
0 1 2 _ _ _ _ 024
0 1 _ 3 4 5 6 025
0 1 _ 3 4 5 _ 026
0 1 _ 3 4 _ 6 027
Table 18: Point Assignments (continued)
POPIT Switch
Setting
Point
#
0 1 _ 3 4 _ _ 028
0 1 _ 3 _ 5 6 029
0 1 _ 3 _ 5 _ 030
0 1 _ 3 _ _ 6 031
0 1 _ 3 _ _ _ 032
0 1 _ _ 4 5 6 033
0 1 _ _ 4 5 _ 034
0 1 _ _ 4 _ 6 035
0 1 _ _ 4 _ _ 036
0 1 _ _ _ 5 6 037
0 1 _ _ _ 5 _ 038
0 1 _ _ _ _ 6 039
0 1 _ _ _ _ _ 040
0 _ 2 3 4 5 6 041
0 _ 2 3 4 5 _ 042
0 _ 2 3 4 _ 6 043
0 _ 2 3 4 _ _ 044
0 _ 2 3 _ 5 6 045
0 _ 2 3 _ 5 _ 046
0 _ 2 3 _ _ 6 047
0 _ 2 3 _ _ _ 048
0 _ 2 _ 4 5 6 049
0 _ 2 _ 4 5 _ 050
0 _ 2 _ 4 _ 6 051
0 _ 2 _ 4 _ _ 052
0 _ 2 _ _ 5 6 053
0 _ 2 _ _ 5 _ 054