D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 122
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
29 Non-Expanded Off-Normal Test Report: Non-Expanded Off-Normal Test Report Events are only
sent when any point is in the off-normal state from any area, but only sends the Off Normal Test
Report Event. Any system trouble that is active also generates a Non-Expanded Off-Normal Test
Report.
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is
generated and the Non-Expanded Off-Normal Test Report is not sent.
To meet UL 864 daily Test Report requirements (when using two phone lines), you must still use
Sked Function Code 9, Test Report and program it to occur on a daily basis as per AHJ
requirements.