D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 36
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
2.7 Miscellaneous
Duress Type
Default: 0
Selection:
0, 1, 2, or 3
0 Do not send a duress event with any
passcode.
1 Increase the last digit by 1 to generate an
alarm. For example, if the passcode is 6123,
6124 activates a duress alarm.
If the last digit of the passcode is 0, a duress
alarm occurs when the user enters 1 as the
last digit of the passcode.
If the last digit of the passcode is 9, a duress
alarm occurs when the user enters 0 as the
last digit of the passcode.
2 Increase the last digit by 2 to generate an
alarm. For example, if the passcode is 6123,
6125 activates a duress alarm.
If the last digit of the passcode is 8, a duress
alarm occurs when the user enters 0 as the
last digit of the passcode.
If the last digit of the passcode is 9, a duress
alarm occurs when the user enters 1 as the
last digit of the passcode.
3 Send a Duress event when any Passcode with
L# Send Duress set to Yes is entered.
This program item determines when a passcode
entry with L# Send Duress authority should produce
a duress alarm.
Duress is enabled in Area Parameters by
setting A# Duress Enable to Yes.
The duress alarm activates when a user
enters the duress passcode followed by
the termination keys ([ESC] or [ENT]).
For SIA CP-01 Compliance
Duress Type must be set to 3.
Cancel Report
Default: No
Selection:
Yes or No
Yes Send Cancel and Fire Cancel
Reports according to routing.
No Do not send Cancel and Fire Cancel
Reports.
A Cancel and Fire Cancel Report is created when a
passcode is entered to silence an Alarm Bell or a Fire
Bell before the bell time expires.
For SIA CP-01 Compliance
This prompt must be set to Yes.
Call for Service Text
Default: Refer to the program record sheet
Selection:
Twenty alphanumeric characters
Enter the text to display on a D1260 series keypad
when the control panel is out of service.
2.8 Area Parameters
This programming module contains three
programming categories: Area Parameters, Bell
Parameters, and Open/Close Options.
2.8.1 Area Parameters
Enter the area number you are programming.
Area# Area On
Default: Yes (Area 1 only)
Selection:
Yes or No
Yes Enable area.
No Disable area.
Use this program item to enable or disable the area
specified.
Refer to Keypad Programming of Area # On and
Area# Account Number on page 37.