23
Log Event Definitions
AC FAIL - AC power to the panel interrupted.
AC RSTOR - AC power to the panel restored.
ALARM - Alarm at point in area specified.
AUTO - Event Modifier for BYPASS event. Indicates four alarms
or troubles in one clock hour caused automatic (swinger) bypass.
BAD CALL - System tried to call Remote Account Manager and
failed.
BATT LOW - Panel battery is below 11.7 VDC.
BATT MISS - Panel battery disconnected or discharged.
BATT RSTOR - Panel battery recharged.
BUS RSTOR - Data Expansion Loop for off-board points
restored.
BUS TRBLE - Data Expansion Loop for off-board points faulted.
BYPASS - Point bypassed. An event modifier showing how the
point was bypassed follows this event in the log.
CANCEL - User canceled an alarm from the area specified.
CKSUM FAIL - Panel programming corrupted. Call for service.
COMM FAIL - Panel could not communicate using phone line
reported.
COMM RSTOR - The communication problem with the phone line
indicated resolved.
DATE CHG - User changed panel’s date and/or time.
EXTRA PT - Incorrectly programmed point connected to system.
FIRE ALARM - Fire alarm at point in area specified.
FIRE END - Fire Walk Test ended.
FIRE RSTOR - Fire alarm at point specified restored.