Installation, Operation, and Maintenance Manual
Greensource CDi Series TW Model Water-to-Water Heat Pumps
Greensource
8733954853 (2020/04)
TW025 | TW035 | TW049 | TW061 | TW122

Questions and Answers

  • J
    John ChanAug 7, 2025
    How to troubleshoot a Bosch Heat Pump that does not run?
    • A
      Angela AllenAug 7, 2025
      If your Bosch Heat Pump isn't running, first ensure the power supply is on by closing the disconnect. If that doesn't work, check for a blown fuse or tripped breaker and replace or reset it, making sure fuses are the correct size. Finally, verify the voltage supply; if it's below the minimum specified on the unit's data plate, contact your local power company.
  • N
    nsandersAug 17, 2025
    What to do if my Bosch Greensource TW122 Heat Pump turns off due to high-pressure control?
    • A
      Alexis BradfordAug 17, 2025
      If your Bosch Heat Pump shuts off due to high pressure, the discharge pressure might be too high. If in cooling mode, check for lack of water flow, excessively warm entering water temperature, or a scaled/plugged condenser. If in heating mode, check for inadequate load side fluid flow. Also, the unit might be overcharged with refrigerant, in which case you should reclaim refrigerant, evacuate, and recharge to the factory-recommended level. Check the high-pressure switch for defects or improper calibration. Furthermore, if your unit uses a UMC and a 40°F freeze sensor, this sensor being in series with the HP switch can register as a high-pressure fault.
  • A
    Ashley ThomasAug 23, 2025
    What causes a Bosch Greensource TW122 Heat Pump to turn off due to low-pressure control?
    • S
      Stephanie SullivanAug 23, 2025
      If your Bosch Heat Pump shuts off due to low pressure, the suction pressure might be too low. If in cooling mode, check for inadequate source-side fluid flow or excessively cold entering water temperature. If in heating mode, check for inadequate water flow, excessively cold entering water temperature, or a scaled/plugged condenser. Also, the unit might be low on refrigerant; check for leaks, repair them, evacuate, and recharge to the factory-recommended level. Inspect the low-pressure switch for defects or improper calibration. If your unit uses a UMC and the DPS option, this sensor being in series with the LP switch can register as a low-pressure fault.
  • R
    regina73Aug 27, 2025
    How to fix no flow or low flow in my Bosch Heat Pump?
    • L
      Lisa CruzAug 27, 2025
      If your Bosch Heat Pump has no or low flow, check the power supply and ensure the on/off switch is in the 'ON' position. Engage the heat pump contactor and inspect for broken or loose wires, repairing or tightening them as needed. Purge any air from the piping system. Remove the pump cartridge and clean it if the pump shaft/impeller is stuck. If the pump is defective, replace it. Finally, repair any kinks in the water piping and ensure it's the proper size.
  • J
    Jennifer PetersenSep 1, 2025
    Why does my Bosch Heat Pump keep short cycling?
    • R
      Rebecca SalinasSep 2, 2025
      If your Bosch Heat Pump is short cycling, first recalculate the heating and cooling loads to ensure the unit isn't oversized. If the thermostat is near a supply air grill, relocate it and adjust the heat anticipator. Check the wiring and controls, looking for a defective or improperly calibrated low-pressure switch.
  • T
    Tanner CarterNov 11, 2025
    Why is my Bosch Heat Pump not cooling or heating sufficiently?
    • R
      Robert TateNov 11, 2025
      If your Bosch Heat Pump isn't providing enough cooling or heating, start by checking for adequate fluid flow. Also, examine the refrigerant charge, as a low charge can cause inefficient operation. Inspect the compressor for defects—if the discharge is too low and suction pressure is too high, the compressor may not be pumping correctly and may need replacement. Also, the refrigerant system may be contaminated with moisture or non-condensables. Reclaim refrigerant, replace filter dryer, evacuate the refrigerant system, and recharge with factory recommended charge. Other potential issues include a defective reversing valve (creating a bypass), TXV issues (restrictions or defects), and incorrect operating pressures (compare to the unit's pressure/temperature chart). Finally, recalculate heati...

Summary

Safety Warnings

General Safety Precautions

Outlines critical safety advice for installation and maintenance.

Unit Installation Topics

Installation and Piping Requirements

Instructions for mounting the unit and connecting water piping.

Electrical Installation

Specific Application Considerations

Well Water Systems

Guidance on using well water, including material choice and flow.

Cooling Tower;Boiler Systems

Considerations for connecting to cooling tower or boiler water loops.

Post-Installation System Checkout

System Checkout Procedure

Checklist of critical steps for post-installation verification.

Unit Start-Up and Operation Sequence

Steps for starting the unit and understanding its operational modes.

Heat Recovery Package (HRP) Setup

Safety Devices and UPM Controller

UPM Controller Overview and Safety Features

Description of the UPM's function and its safety controls.

Safety Devices and UPM II Controller (TW122)

UPM II Controller Overview and Safety Controls

Description of UPM II function and its safety controls.

Water-To-Water Unit Controller

Heating, Cooling, and Auto-Changeover Modes

How the controller manages heating, cooling, and auto-changeover.

Unit Protection Mechanisms

Explanation of the controller's protection against faults.

Low-Temperature Loop Application

Check-Out Sheet

Troubleshooting Unit Issues

Unit Troubleshooting Guide

Table of problems, causes, and checks for unit operation.

Insufficient Cooling;Heating and HRP Troubleshooting

Addresses issues like low flow, insufficient output, and HRP problems.

Maintenance and Decommissioning

Wiring Diagrams

Bosch Greensource TW122 Specifications

General IconGeneral
ModelGreensource TW122
CategoryHeat Pump
Heating Capacity12.2 kW
Energy Efficiency Class (Heating)A++
Sound Power Level (Outdoor Unit)62 dB(A)
RefrigerantR410A
Operating Temperature Range (Heating)-20°C to +35°C
Operating Temperature Range (Cooling)+10°C to +46°C