Installation, Operation, and Maintenance Manual
Greensource CDi Series TW Model Water-to-Water Heat Pumps
Greensource
8733954853 (2020/04)
TW025 | TW035 | TW049 | TW061 | TW122

Questions and Answers

  • T
    Taylor CampbellAug 3, 2025
    How to troubleshoot a Bosch Heat Pump that does not run?
    • C
      caitlin58Aug 3, 2025
      If your Bosch Heat Pump isn't running, first ensure the power supply is on by closing the disconnect. If that doesn't work, check for a blown fuse or tripped breaker and replace or reset it, making sure fuses are the correct size. Finally, verify the voltage supply; if it's below the minimum specified on the unit's data plate, contact your local power company.
  • D
    dfoxAug 13, 2025
    What to do if my Bosch Greensource CDi TW Heat Pump turns off due to high-pressure control?
    • R
      Robert AndersonAug 13, 2025
      If your Bosch Heat Pump shuts off due to high pressure, the discharge pressure might be too high. If in cooling mode, check for lack of water flow, excessively warm entering water temperature, or a scaled/plugged condenser. If in heating mode, check for inadequate load side fluid flow. Also, the unit might be overcharged with refrigerant, in which case you should reclaim refrigerant, evacuate, and recharge to the factory-recommended level. Check the high-pressure switch for defects or improper calibration. Furthermore, if your unit uses a UMC and a 40°F freeze sensor, this sensor being in series with the HP switch can register as a high-pressure fault.
  • M
    Matthew SextonAug 18, 2025
    What causes a Bosch Greensource CDi TW to turn off due to low-pressure control?
    • A
      Amy FaulknerAug 18, 2025
      If your Bosch Heat Pump shuts off due to low pressure, the suction pressure might be too low. If in cooling mode, check for inadequate source-side fluid flow or excessively cold entering water temperature. If in heating mode, check for inadequate water flow, excessively cold entering water temperature, or a scaled/plugged condenser. Also, the unit might be low on refrigerant; check for leaks, repair them, evacuate, and recharge to the factory-recommended level. Inspect the low-pressure switch for defects or improper calibration. If your unit uses a UMC and the DPS option, this sensor being in series with the LP switch can register as a low-pressure fault.
  • S
    Sean BrownAug 23, 2025
    How to fix no flow or low flow in my Bosch Greensource CDi TW Heat Pump?
    • A
      Andrea WhiteAug 23, 2025
      If your Bosch Heat Pump has no or low flow, check the power supply and ensure the on/off switch is in the 'ON' position. Engage the heat pump contactor and inspect for broken or loose wires, repairing or tightening them as needed. Purge any air from the piping system. Remove the pump cartridge and clean it if the pump shaft/impeller is stuck. If the pump is defective, replace it. Finally, repair any kinks in the water piping and ensure it's the proper size.
  • K
    Kevin CraneAug 27, 2025
    Why does my Bosch Heat Pump keep short cycling?
    • C
      Charles RiggsAug 28, 2025
      If your Bosch Heat Pump is short cycling, first recalculate the heating and cooling loads to ensure the unit isn't oversized. If the thermostat is near a supply air grill, relocate it and adjust the heat anticipator. Check the wiring and controls, looking for a defective or improperly calibrated low-pressure switch.
  • J
    Jason HillNov 7, 2025
    Why is my Bosch Greensource CDi TW Heat Pump not cooling or heating sufficiently?
    • S
      Sandra GreenNov 7, 2025
      If your Bosch Heat Pump isn't providing enough cooling or heating, start by checking for adequate fluid flow. Also, examine the refrigerant charge, as a low charge can cause inefficient operation. Inspect the compressor for defects—if the discharge is too low and suction pressure is too high, the compressor may not be pumping correctly and may need replacement. Also, the refrigerant system may be contaminated with moisture or non-condensables. Reclaim refrigerant, replace filter dryer, evacuate the refrigerant system, and recharge with factory recommended charge. Other potential issues include a defective reversing valve (creating a bypass), TXV issues (restrictions or defects), and incorrect operating pressures (compare to the unit's pressure/temperature chart). Finally, recalculate heati...

Summary

Document Conventions and Safety

Key to Symbols

Identifies symbols like DANGER, WARNING, CAUTION, NOTICE, and Important Information.

Safety Warnings

Provides critical safety instructions and precautions for installation and servicing.

Unit Installation

Installation Procedures

Covers moving, storage, inspection, location, piping, and electrical connections.

Application Considerations

Details for well water, cooling tower, boiler, and geothermal systems.

System Operation and Control

System Operation and Startup

Covers checkout, start-up, sequence of operation, and controller features/modes.

Heat Recovery Package (HRP)

Details on HRP setup, operation, and initial startup.

Troubleshooting and Maintenance

Troubleshooting Guide

Lists common problems, causes, and solutions for unit and HRP operation.

Maintenance Procedures

Annual checkups, refrigerant handling, and decommissioning guidelines.

Technical Specifications

Wiring Diagrams

Electrical schematics for unit connections and components.

Dimensional Drawings

Physical dimensions and connection port details for unit models.

Terminology

Definitions of acronyms and key terms used throughout the manual.

Bosch Greensource CDi TW Series Specifications

General IconGeneral
BrandBosch
ModelGreensource CDi TW Series
CategoryHeat Pump
LanguageEnglish

Related product manuals