EasyManuals Logo

Bosch Greensource CDi TW Series User Manual

Bosch Greensource CDi TW Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
Greensource CDi Series TW
Greensource CDi Series TW Model8733954853 (2020/04) Subject to change without prior notice
30 | Water Quality Table
WATER QUALITY TABLE
Table 8 Water Quality
Water Quality
POTENTIAL
PROBLEM
Water Characteristic Acceptable Value
Copper Cupro-Nickel
pH (Acidity/Alkalinity) 7–9 7–9
SCALING
Hardness (CaCO
3
, MgCO
3
)
< 350 ppm < 350 ppm
Ryznar Stability Index
6.0–7.5 6.0–7.5
Langelier Saturation Index
-0.5 – +0.5 -0.5 – +0.5
CORROSION
Hydrogen Sulfide (H
2
S)
< 0.5 ppm* 10–50 ppm
Sulfates
< 125 ppm < 125 ppm
Chlorine
< 0.5 ppm < 0.5 ppm
Chlorides
< 20 ppm < 150 ppm
Carbon Dioxide
< 50 ppm < 50 ppm
Ammonia
< 2 ppm < 2 ppm
Ammonia Chloride
< 0.5 ppm < 0.5 ppm
Ammonia Nitrate
< 0.5 ppm < 0.5 ppm
Ammonia Hydroxide
< 0.5 ppm < 0.5 ppm
Ammonia Sulfate
< 0.5 ppm < 0.5 ppm
Dissolved Solids
< 1,000 ppm < 1,500 ppm
IRON FOULING
Iron (Fe
2
+ Iron Bacteria
Potential)
< 0.2 ppm < 0.2 ppm
Iron Oxide
< 1 ppm < 1 ppm
EROSION
Suspended Solids < 10 ppm, < 600 µm size** < 10 ppm, < 600 µm size**
Maximum Water Velocity
6 ft/sec 6 ft/sec
* No "rotten egg" smell present at < 0.5 ppm H
2
S.
** Equivalent to 30 mesh strainer

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Greensource CDi TW Series and is the answer not in the manual?

Bosch Greensource CDi TW Series Specifications

General IconGeneral
BrandBosch
ModelGreensource CDi TW Series
CategoryHeat Pump
LanguageEnglish

Related product manuals