Commercial Series TriTech+ Motion Detector with
20 en | Wiring
Anti-mask
1
2
3
4
12 k
2.2 k
1.0 k
2.2 k
33 k
J
2.2 k
1.0 k
NC
NC
T T
TR TR
NC NC
T
T TRTR
3
Figure6.5: Alarm loop jumpers overview
Trouble resistors (pin block section 4)
Use the selection pins marked with “4” when wiring to control panels with the following
configuration: dual or triple EOL resistor.
When placing a jumper across the desired pins, the corresponding resistance value is
connected in parallel with the trouble contact.
During normal operation, the trouble contact is in either shorted condition or alarm resistance
value condition.
The available resistance values are 2.2 kΩ and 12 kΩ.
1
2
3
4
12 k
2.2 k
1.0 k
2.2 k
33 k
J
2.2 k
1.0 k
NC
NC
T T
TR TR
NC NC
T
T TRTR
4
Figure6.6: Trouble resistors overview
2017.09 | 03 | F.01U.309.350 Reference Guide Bosch Security Systems, Inc