An overload or short circuit in the secondary / auxiliary
outputs, RCP outputs, or volume override outputs will
not:
affect the main 24V output.
cause other outputs to shut down.
If two secondary outputs are overloaded, this may lead
to loss of the third auxiliary output.
If the battery voltage is below 16 V, this is treated as a
fault.
If the current limiter is activated, it will switch the
output off. When the output is disconnected, by either
the current limiter or under voltage protection, the
charger can be reset by turning it off and then back on
again.
Note
If the main 24 V output is shut off, the secondary
24 V is also switched off.
Note
If an over current or short circuit in the main 24V
output causes the current limiter to shut down
the output, the secondary outputs will also be
switched off.
Note
If the charger activates the under voltage
protection, but the mains is not restored, turning
the unit off and then back on again will also
reset the charger.