Fig.5-18: Fuses F4 and F5
Replacing fuses F4 and F5
1. Switch off power voltage to drive system.
2. Wait at least 30 minutes until discharge time has elapsed.
3. Open fuse carriers F4 and F5.
4. Remove fuses F4 and F5.
Note: Always replace both fuses, even if only one of them is defective.
Probably, the intact fuse is already damaged.
5. Insert new WP-30A14Fa fuses by BUSSMANN.
6. Close fuse carriers F4 and F5.
DOK-INDRV*-KCU02*UL***-IN01-EN-P
Rexroth IndraDrive Mi Electronic Control System KCU02
Bosch Rexroth AG 45/69