Time Base
Choose one of the options in the table below for the time base.
Option Description
1
20
0 ms
2 1 Second
3
1 Minute
4 1 Hour
Time Base Multiplier
Enter a value between 01 – 99.
One Shot Mode
When you program the output polarity as a one shot, the time base is multiplied by the time base multiplier (eg.
If the time base = 2 and the multiplier = 05, the output will operate for 5 seconds)
Pulsing Mode
When you program the output polarity as pulsing, the time base becomes the ‘ON’ time and the multiplier
becomes the ‘OFF’ time. The ‘OFF’ time is the time base x the multipl
ier (eg. If you want the output to pulse
one (1) seco
nd ‘ON’ and five (5) seconds ‘OFF’, you would program time base as one (1) and the multiplier as
five (5)).
Solution Ultima 880
Quick Reference Guide 15
Bosch Security Systems Pty Limited
Polarity (Modes)
Option Description Option Description
0
Disable
d
1
Norma
lly Open, Going Low
8
N
ormally Low
, Going Open
2 Normally Open, Pulsing Low 9 Normally Low, Pulsing Open
3
Normal
ly Open, One Shot Low
10
Normally Low, One Shot Open
4 Normally Open, One Shot Low (Reset) 11 Normally Low, One Shot Open (Reset)
5
Normal
ly Open, One Shot Low (Re-trigger)
12
Normally Low, One Shot Open (Re-trigger)
6
Norma
lly Open, One Shot Low (Alarm)
13
Normally Low, One Shot Open (Alarm)
7
Norma
lly Open, Latching Low
14
Normally Low, Latching Open