SSB 6720866942 (2018/06) US
VENTING SIZE DATA | 57
Appendix I - Venting size data
SSB 800 SA
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,21 0,02 0,21 0,02
Flue temperature °F 167 147,2 104 89,6
Max. pressure at boiler exit in. wc 0,83 0,04 0,72 0,03
SSB 1000 SA
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,26 0,02 0,26 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,91 0,05 0,83 0,03
SSB 1000 TL
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,26 0,02 0,53 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,96 0,05 0,86 0,03
SSB 1000 TL2
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,53 0,02 0,53 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,91 0,05 0,82 0,03
SSB 1000 TL3
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 0,79 0,02 0,79 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,79 0,05 0,71 0,03
SSB 1000 TL4
Unit
T supply / return (°F): 176 / 140 T supply / return (°F): 104 / 86
Maximum Input Minimum Input Maximum Input Minimum Input
CO
2 % 9 9 9 9
Exhaust gas mass (weight) lb/s 1,06 0,02 1,06 0,02
Flue temperature °F 176 152,6 104 91,4
Max. pressure at boiler exit in. wc 0,59 0,05 0,51 0,03