Table 9 – Operation conditions
Power reduction in case of high temperature risk
A control strategy was implemented in the fix power version (manual selection of segments to
increase power) to avoid overheating of the water when a high power is selected on the power
selector and low water flow is running through. To avoid scalding hazard,
the water heater perform as follows:
- If the power selector is in level 2 or 3 and the outlet temperature is expected to be
higher than 70ºC, the control unit must automatically decrease the power level. “E1”
warning code must be shown blinking with a frequency of 2Hz, so the user is aware
that the water heater has automatically decreased power;
- After this, even if the water flow is increased, the water heater shall not increase
power again.
- The reset of the warning will only be possible by closing of the water tap;
- If the outlet temperature is higher than 70ºC for more than 20 seconds or if a
temperature higher than 85ºC is achieved (either for level 1, 2 or 3), the water heater
is expected to lockout with “E1” error. If “E1” error has occurred, manual reset is
needed to resolve it
Power reduction at start-up (specific for 11L)
A control strategy was implemented to avoid overheating of the water when a high power is
selected on the power selector and low water flow is running through at start-up. To avoid
scalding hazard, the water heater must perform as follows:
- If the power selector is in level 3 and the water flow at start-up is lower than 4 l/min,
the control unit must automatically decrease the power level to level 2.