3.2 Water connections
Requisite
Observations
Water pipes were cleaned
before connected to the
appliance?
Leakage test was done
successfully?
Inlet water filter was checked
and is cleaned, ensuring the
necessary water flow?
Accessories for water
connections are adequate?
Water pressure and flow are
according to the appliance
specifications?
- Nominal pressure: 1- 4 bar
- Minimum pressure: 0,15 bar
- Maximum pressure: 12 bar
Table 3 Check list hydraulic connections
3.3 Gas connection
Requisite
Confirmation
The appliance is suitable for the available gas type?
Pressure reducer and gas pipe are adequate for the required
pressure and gas flow?
Accessories for gas connection are adequate and according to
the country specification/standards?
Table 4 Check list for gas connections
3.4 Flue Exhaustion
The correspondent appliance manual have indicated the maximum flue length according model
and flue type orientation, nevertheless there is with this new line a new approach where for flue
lengths > 4 m it will be required to have configured in HMI a parameter to indicate to
Flue Exhaustion > 4 m (Note: only for MPP2 (with water valve))
Access menu AA.
Scroll until find F9.
Press ok
Scroll and select the flue length
Press ok
Length selected
Model
Flue Length
Parameter
12
0 4 m
00
4 8 m
01
8 12 m
02
15
0 8 m
00
17
0 4 m
00
5 9 m
01
Table 5 Flue Configurations