Installer Guide 6
Heat Pump Systems
Typical Wiring Configurations
NOTE: The “System Type” option will be configured in the Installer Settings section. The 6100 is a single stage
thermostat and not intended for multi stage equipment.
1 HEAT / 1 COOL - No Auxiliary Heat
Set System Type to 11HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve [note 2]
Y1 CompressorRelay(appearsasYonthe6100)
G FanRelay
C 24VoltACTransformerCommon [note 1]
3 HEAT / 2 COOL – Including Auxiliary Heat
Set System Type to 32HP
Rh 24VoltACPower
Rc
ConnectedtoRhwithsuppliedJumperWire
O/B ChangeoverValve [note 2]
Y1
Compressor1Relay(1ststageheating/cooling)
Y2
Compressor2Relay(2ndstageheating/cooling)
AUX1/E
AuxiliaryHeatRelay(3rdstageheating)
/Emergency
Heat[note 5]
E EmergencyHeatRelay [note 5]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
2 HEAT / 1 COOL - Including Auxiliary Heat
Set System Type to 22HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve[note 2]
Y1 CompressorRelay(1ststageheating/cooling)
W2
AuxiliaryHeatRelay(2ndstageheating)[note 3]
E EmergencyHeatRelay[note 3]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
2 HEAT / 2 COOL - No Auxiliary Heat
Set System Type to 32HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve[note 2]
Y1
Compressor1Relay(1ststageheating/cooling)
Y2
Compressor2Relay(2ndstageheating/cooling)
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
4 HEAT / 2 COOL - Including Auxiliary Heat
Set System Type to 42HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B ChangeoverValve[note 2]
Y1
Compressor1Relay(1ststageheating/cooling)
Y2
Compressor2Relay(2ndstageheating/cooling)
AUX1/E
AuxiliaryHeatRelay1(3rdstageheating)
/EmergencyHeat[note 5]
AUX2
AuxiliaryHeatRelay2Relay(4thstageheating)
E EmergencyHeatRelay[note 5]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
NOTES - Heat Pump Systems
[1] Optional24VoltACcommonconnection.
[2] O(coolactive)orB(heatactive)isselectedinthe
InstallerSettingsmenu.
[3] InstallaeldsuppliedjumperbetweentheW2/AUX2
andW1/E/AUX1terminalsifthereisnoseparate
emergencyheatrelayinstalled.
[4] IftheLterminalisused,the24VoltACcommon
mustbeconnected(Cterminal).
[5] Ifaseparateemergencyheatrelayisinstalled,the
W1/E/AUX1terminalshouldhaveboththeauxiliary
heat1relayandemergencyheatrelayconnected.