BRINKS BHS 2000A - UL Compliance Verification; Hardware Considerations; Programming Considerations; CSFM Compliance Verification

BRINKS BHS 2000A
31 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UL
COMPLIANCE
VERIFICATION
FOR
BHS-2000A
ALARM
CONTROL
PANEL
Follow
the
instructions
below
when
installing
and
programming
a
BHS-2000A
Alarm
Control
Etael
to
meet
installation
requirements
for
UL
985,
1023,
and
1635.
HARDWARE
CONSIDERATIONS
1.
Do
not
plug
the
Bassler
transformer
(BE116225AA=25VA,
BE114620CAA
=
20VA)
into
a
receptacle
cdhtrolled
by
a
switch.
2.
Use
a
12
volt
minimum
4
AH
battery
(Yuasa
NP4-12)
in
order
to
have
a
standby
time
of
at
least
4
hours.
3.
Use
a
U.L.
listed
speaker
across
terminals
5
and
6.
Do
not
use
speaker
loads
of
less
than
4
ohms.
Supplementary
speakers:
Premier
PTS-15,
Ultrak
DS-2.
4.
Maximum
combined
Auxiliary,
keypad,
and
Fire
current
is
330
mA
at
12.5
VDC
with
a
20VA
transformer.
500
mA
with
a
25
VA
transformer.
5.
Maximum
current
draw
for
the
Bell
output
must
not
fexceed
.5
Amps
using
d
25
VA
transformer
and
.4
Amps
using
a
20
VA
transformer.
Either
bell
of
Siren
should
be
used
as
the
primary
sounding
output.
6.
Use
UL
listed
4-wire
smoke
detectors
and
UL
listed
end-of-line
relay
modules.
7.
Use
P/N
EOL4700
end-of-line
module
(sold
separately)
for
all
fire
zones,
and
Scantronic
(P/N
122-000472
(enclosed
)
for
all
burglary
type
zones
of
protection.
8.
Keypads
must
be
installed
within
the
protected
area.
9.
A
UL
listed
tamper
switch
must
be
installed
on
the
control
panel
cabinet.
PROGRAMMING
CONSIDERATIONS
1.
Maximum
Exit
time
allowed
is
60
seconds.
2.
Maximum
Entry
time
allowed
is
45
seconds.
3.
Program
the
panel
to
report
to
the
Central
Station
on
loss
of
AC
power
and
Low
battery.
4.
Program
all
burglary
sounding
devices
to
operate
for
a
minimum
of
4
minutes.
5.
"No
E.O.L.R"
resistor
mode
must
not
be
enabled
to
meet
UL
Grade
A
requirements.
EOLR's
must
be
used
on
all
zones.
6.
Program
manual
shut
down
for
the
fire
alarm
time
out.
7.
Dialing
attempts
for
phone
1
&
2
must
be
a
minimum
of
5
and
a
maximum
of
10
attempts.
8.
Test
message
interval
must
be
programmed
to
1
every
24
hours.
9.
False
alarm
prevention
must
be
disable
(load
shed).
10.
For
UL
applications,
the
system
must
be
programmed
so
that
the
master
code
can
not
be
altered
by
the
user
form
the
keypad
(Location
156,
master
code
reprogrammabilty).
11.
Program
the
panel
to
report
all
Fire
zone
Trouble
conditions
to
the
Central
Station.
12.
24
hour
fire
zones
cannot
be
programmed
as
bypassable
zones.
13.
For
correct
dialer
report
prioritizaiton,
Fire
zones
are
to
be
assigned
to
the
lower
numbered
zones,
Panics
on
the
next
lowest
numbed
zones
and
burglary
zones
on
the
highest
numbers.
Example:
Zone
1
=
Fire
Zone
2
=
Panic,
Zone
3-8=
Burglary.
14.
Maximum
dialer
delay
time
is
45
seconds.
C.S.F.M,
COMPLIANCE
VERIFICATION
For
C.S.F.M.
residential
fire
installations,
a
Power-Sonic
12V
8AH
battery
(Model
PS-1282L)
must
be
used
in
order
to
achieve
a
battery
back
up
time
of
24
hours.
Maximum
current
draw
for
the
Auxiliary
and
Bell
outputs
are
as
follows:
Auxiliary,
Fire,
and
Keypad
=
182
mA
Bell
output
=
1
amp.
Siren
output
=
4
ohms
maximum.
Note
:
Either
bell
or
siren
output
should
be
used
as
the
primary
sounding
output.
30