Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
86
Trident Water Management System
(cont.)
Trident Test Procedure & Service Checks
(cont.)
Wet Tank Test:
Commence filling the tank with water then:
Check the pump operates when water makes closed circuit at the Common and
Low Water Level Sensor probes.
Check for voltage drop (must be less than 9 Volt) across the Common (black)
Water Sensor probe and the Low Water Level (white) probe.
Check that the water doesn't overflow out the drain tube before the water reaches
the High Water Level Sensor.
Check for voltage drop (must be less than 9 Volt) across the Common (black)
Water Sensor probe and the High Water Level (red) probe.
Refer to diagrams on pages 75 and 76.
If voltage doesn't drop below 9 Volts:
Check for coating on the Water Sensor probes preventing circuit.
Check for high water quality (not able to make circuit - refer to Brivis).