Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
70
Cooler Operation
(cont.)
Water Inlet Solenoid Operation
(cont.)
Water inlet solenoid does not turn OFF
Check the water inlet solenoid closes within 5 seconds of turning the 240 Volt
power OFF.
Check the Trident wiring loom is connected to the N-E5 and the plug connection is
good.
Check the Trident loom circuit output and water contact sensitivity at both the
probe and the N-E5 plug terminals (see test procedure Trident Water Management
section)
If loom not connected (open circuit)
N-E5 Error 50 - Water inlet solenoid open for 15 minutes before lockout.
Check that the water inlet solenoid is not energised (240 Volt) at the WATER INLET
SOLENOID-ACTIVE & NEUTRAL terminals.
If power present:
Check if the Networker is turned ON and cooling required.
Check the Cooler water level is not at a level that requires the water inlet
solenoid to be energised.
Check the Cooler is not in a pre-program operation, requiring the water inlet
solenoid to be operating i.e. wash or flush function.
If no power:
Check the water inlet solenoid has not blocked or jammed open.