EasyManua.ls Logo

BRONKHORST EL-FLOW Base Series - Page 20

BRONKHORST EL-FLOW Base Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BRONKHORST®
Page 20 EL-FLOW Base Series Mass Flow Controllers 9.17.061
Once the DDE server is active, open the FlowDDE Test Form via the menu (as shown below) or by
pressing <F6>.
The following screen appears:
To read/change the slave address, parameter 199: Bus address must be selected. To read/change the
baud rate, parameter 201: Baudrate must be selected. And to read/change the parity parameter 335:
Bus1 Parity must be selected. To change one of these parameters parameter 7: Initreset has to be set to
‘64’ first.
Valid values for the slave address are between 1 and 247, valid values for the baud rate are 9600, 19200
and 38400, valid values for parity are 0 (= None), 1 (= Odd) and 2 (= Even). The changed values will be
effective immediately after changing.
In case of OEMD2 hardware revision (“OEMD2” text on the instrument label):
To read/change the slave address, parameter “309: Fieldbus2 address must be selected. To
read/change the baud rate, parameter “310: Fieldbus2 baudrate must be selected. And to read/change
the parity parameter “336: Fieldbus2 parity must be selected. To change one of these parameters
parameter 7: Initreset has to be set to ‘64’ first.

Table of Contents

Other manuals for BRONKHORST EL-FLOW Base Series

Related product manuals