EasyManua.ls Logo

BRV ModvlvS Logico - Specifications

BRV ModvlvS Logico
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Electrical specifications:
Power supply 100 - 240VAC, 50 - 60 Hz
Power consumption / standby 0.5 - 2.5 W/ 0.5
Total switched power 2 A
Switched power per relay 480
Internal fuse 1 2 A slow 250V
Protection category IP40
Protection class / overvoltage category II / II
Inputs/Outputs
Sensor inputs 6 Pt1000 -40 °C ... 300 °C
Sensor inputs VFS / RPS Grundfos Direct Sensor C-100°C (-25°C /120°C short term)
Number room thermostats per cir-
cuit
8 °CALEON /
°CALEON Clima
! Up to 8 ° CALEON / ° CALEON Clima
can be supplied with voltage from the
controller!
Sensor inputs RC20 2 Pt1000
Outputs mechanical relay 4
of relay potential free R4 1
mechanical relay R1 - R4 460VA for AC1 / 460W for AC3
0-10V/PWM output V1 - V2 for 10 k Ω working resistance 1 kHz, level 10 V
+ Terminal/
24V voltage output
+ Max. load by external
devices 24V / 6W
Max. cable length
VFS/RPS sensors <3m
CAN <3m; at >=3m, a shielded twisted-pair cable is to be
used and connected to the protective conductor on one side.
0-10V/PWM <3m
mechanical relay <10m
Interface
Fieldbus CAN
Permissible Ambient Conditions
for controller operation 0 °C - 40 °C, max. 85 % rel. humidity at 25 °C
for transport/storage 0 °C - 60 °C, no moisture condensation permitted
Other Specifications and Dimensions
Housing design 2-part, ABS plastic
Installation methods Wall installation, optionally panel installation
Overall dimensions 163 mm x 110 mm x 52 mm
Aperture installation dimensions 157 mm x 106 mm x 31 mm
Display Fully graphical display, 128 x 64 dots
Light diode multicolour
Real Time Clock RTC with 24 hour power reserve
Operation 4 entry keys